HYDRO-TEMP PART NUMBER - 4T760 (2 STAGE) TYPICALLY USED TO CONTROL WATER HEATING OR COOLING. Quick Setup instructions for Honeywell 2 & 4 Stage Set
point These instructions will explain how to set up the Honeywell set point to control heating and cooling with a 4 stage set point. 1. Wire the main power and the remote sensor to the Honeywell set point. Refer to the front cover on the set point for proper wiring. (Power and sensor must be wired to program set points) 2. Turn on the power supply. When power in applied and the sensor is attached, the system will start a 3 1/2 minute count down. You can bypass this by pressing any key. It will then display the current sensor temperature and the stages calling on the lower right corner. 3. Set the stages for heating and or cooling.
4. Set the Temperature you desire for each stage and the differential.
***** Note: After any change you must press the enter
button to save the change into the microprocessor of the Honeywell Set points. For most Hydro-Temp applications where we turn on and off zone valves for well water we will set two set points for heating and two for cooling. Normal set points would be: Stage 1 - Heating - 52ºF with 2º
Diff. |