Updates between version 1.10 to version 1.11
version 1.11 of the firmware was released
3-19-2012
Log Program
Updates between version 1.13 to version 1.14
version 1.14 of the firmware was released
8-22-2010
Firmware Program
-
Fixed an issue where when no humidity sensor is present and
dehumidification is turned on, the system no longer overdrives the blower.
-
Added a limit so when overdriving the blower, the fan speed
cannot exceed 100% of rated CFM.
Updates between version 1.12 to version 1.13
version 1.13 of the firmware and 1.12 of the setup program was released
6-8-2010
Firmware Program & Setup Program
Updates between version 1.10 to version 1.12
version 1.12 of the firmware was released 10-19-09
Firmware Program
-
Fixed a bug that prevented F1, F2, F3 relays
from working correctly when in test mode.
-
Enhanced dehumidification system.
-
Fixed a bug that allowed a sensor family
category with a missing sensor to still report temperatures.
-
Modified IrDA protocol to send RH, fan, and
stage information to PDA.
Toolbox Program
- Updated sensor data page to display set points,
differentials, fan speed, humidity, and a system status summary at the
bottom.
- Words and icons on command page now launch tools like the
icons did in previous versions making these utilities much more user
friendly.
Updates between version 1.01 to version 1.10
Version 1.01
was
released 12-3-08. Version 1.10 was released 6-24-09
Setup Program
- Many small bugs fixed that are not visible.
- Changed wording to make description of adjustments more
comprehensible.
- Added ability to transfer setup settings from Palm to
Palm.
- Added Cool on and Heat on to relay output on special
screen.
- Combined DHW and AHW screens, added drop down box to
switch within these screens.
- Fixed max temp on hot water screen so it can't be
adjusted lower then the other settings.
- Removed percentages from cooling, heating, and blower
screens leaving only CFM values.
- Fixed security bug that would not allow you to enter
Factory level until next day.
Firmware Program
- Added ability to transfer firmware from Palm to Palm.
Toolbox Program
Logs Program
Updates between version 1.0 to version 1.01
Version 1.0
was
released 9-25-08. Version 1.01 was released 12-3-08
Setup Program
- Many small bugs fixed that are not visible.
- Revised buttons and added + and - buttons to change
values.
- Increased security to protect dealers and equipment.
Firmware Program
- Auto import of the firmware software. Before if you
put an updated firmware program on the PDA the first thing you had to do was
an import from hotsync. This is automatic now.
- Checksum added. This feature works in the
background to check the stability of the firmware before, during and after a
download. This will prevent a corrupt download into the control board.
ATL Toolbox Program
- Increased security to protect dealer and equipment.
Updates between version .51 to version 1.0
Version .51 was released on 4-17-08. Version 1.0
was
released 9-25-08
Setup Program
- Many small bugs fixed that are not visible.
- Beefed up signal strength to temperature sensors to fix
occasional sensor problems.
- Humidification implemented in the heating screen to turn
on or off a humidifier. (Requires an extra sensor)
- Dehumidification implemented in the cooling screen to
slow down the blower in the cooling mode to force the unit to dehumidify
more. (Requires an extra sensor)
- Blower settings added to Hardware screen.
- Some slide bars changed to plus or minus buttons to speed
up operation.
- Some settings limited depending on other settings. (for
example the AP start can not be set higher then the AD/AP stop)
- Abort and cancel buttons added to stop communicating
between PDA and Controller if error occurs.
- Progression bar and sounds added to communication window
to help estimate time remaining when up loading or downloading to
controller.
- A save as feature added if your trying to download a
program that already exist.
- Any system with version 1.0 will have a 2 hour maximum
test mode if initiated from the test buttons. After the two hours the
system will exit from test mode and resume running from thermostats.
Continuous test mode can be done from the ATL toolbox program.
Firmware Program
The firmware program has no visible changes made.
ATL Toolbox Program
- The ATL toolbox program was split up into two programs.
You will now have the ATL toolbox program and the Log Program.
- When opened the ATL Toolbox program will list all
previous systems that were looked at by "date"+"time"+"system name".
This way you can view the systems data at a later date or press the open
button to create a new entry.
- When a new file is created you must only download from
the board once by clicking the system info icon then all the
other data is
updated from that download.
- A new button "Service Required Info" was added to
tell the tech why the service required light was on.

- When viewing the temperature sensors page a play button
was added. When pressed the PDA must be aimed at the board so the PDA
can update every 5 seconds new temperature readings. This will
continue until the stop button is pressed. (Very Cool feature)
- Another new button was added "System Test" This
screen (shown on bottom right) allows you to run the system from the PDA. This includes
opening and closing dampers individually, turning on and off pumps,
compressors, blowers, strip heat and almost everything the board controls.
When in system test certain settings will adjust automatically. For
example when the system is set to run in stage 1 the ground loop pump and
blower will be turned on also.
Logs Program (new program split from the ATL Setup)
Upon entering the logs program you will have the option of
opening an existing log or creating a new log. Logs are saved in the PDA
by "system name"+ "date" + "time".
- Some things were added to what is logged. Sample
log shown on right side.
- Button on top right of screen will allow you to sort log
entries in ascending order or descending order.
- Drop down arrow will allow filtering of log entries.
Option include: All, Severe, Important, Updates, & Minor.